BM0-D8 - VOLUME FLOW MODBUS/BACNET DAISY CHAIN (FOR OX) 

Control component with dynamic transducer, Modbus RTU, BACnet MS/TP and double RJ45 connection (daisy-chain wiring) suitable for TROX Ox

Compact unit for VAV terminal unit TVR, TVJ, TVT, TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVM
■ Controller, dynamic differential pressure transducer and actuator in one casing
■ Use in ventilation and air conditioning systems, only with clean air
■ Double RJ45 connection for simple daisy-chain wiring of supply voltage and communication
■ Compatible with field application modules from TROX Oₓ , e.g. FAM-E and FAM-W
■ Volume flow rates qvmin and qvmax are pre-set in the factory and saved in the controller as variable parameters
■ High data transparency thanks to standardised bus communication Modbus RTU or BACnet MS/TP
■ Setpoint specification, override control and parameter adjustment via bus communication or TROX Oₓ Field Application Module
■ Service access for manual adjustment devices and PC configuration software

General information

Application
  • All-in-one control devices for VAV terminal units
  • Dynamic differential pressure transducer, electronic controller, and actuator are combined in one casing
  • Different control tasks through corresponding setpoint specification
  • Room temperature controllers, central building management systems, air quality controllers and others control the variable volume flow control by specifying setpoints via the communication interface
  • Suitable for room control from TROX Oₓ with Field Application Modules, e.g. FAM-E, FAM-W
  • Simple connection thanks to common connection for supply voltage and communication via double RJ45 socket (daisy-chain wiring possible)
  • Up to four volume flow controllers can be connected in series via daisy-chain wiring
  • Override control for activating qvmin, qvmax, shut-off, Open position via Modbus register, BACnet objects or TROX Oₓ possible
  • The actual volume flow rate is available as a network data point
  • The damper blade position is available as a network data point
  • Standard filtration in comfort air conditioning systems allows the controller to be used in the supply air without additional dust protection measures
With heavy dust levels in the room
  • Install suitable extract air filters upstream, as a partial volume flow is routed through the transducer for volume flow measurement
If the air is contaminated by dust, lint, or sticky particles
  • Use a control component with static differential pressure transducer, e.g. BUSN

Control strategy
  • The volume flow controller works independently of duct pressure
  • Pressure fluctuations do not cause any permanent volume flow deviations
  • A dead zone (hysteresis), within which the damper blade is not moved, ensures stable regulation
  • The volume flow range for the controller is factory-set (qvmin: minimum volume flow rate, qvmax: maximum volume flow rate)
  • Operating parameters are defined in the order code and factory-set

Operating modes

  • Modbus RTU: Setpoint specification via TROX Oₓ or external software
  • BACnet MS/TP: Setpoint specification via external software

Interface
Communication interface
  • Modbus RTU, RS485 (factory-set)
  • BACnet MS/TP (can be activated on site with ZTH-EU)
  • Data points, see bus lists

Parts and characteristics
  • Transducer for dynamic pressure measurements
  • Overload-proof actuator
  • Dual RJ45 connector
  • Service interface for service tools
  • Shaft connection via clamping device or positive locking
  • Indicator lights for operating status indication
  • Addressing button for setting participant addresses in bus mode
  • Power supply and communication not galvanically isolated

Operating parameters
  • qvmin = 0 – 100% of the nominal volume flow qvnom can be set
  • qvmax = 20 – 100% of the nominal volume flow qvnom can be set

Construction
Type LMV-D3-M/B-FX TR for volume flow controller
  • TVR
Type LMV-D3-M/B-X TR for volume flow controllers
  • TZ-Silenzio, TA-Silenzio, TVZ, TVA, TVM
Type NMV-D3-M/B-X TR for volume flow controllers
  • TVJ
  • TVT up to 1000x300 or 800x400

Commissioning
  • As the volume flow rates are factory-set, the air terminal units must be installed only at the designated locations
  • Network integration requires commissioning steps
  • Operating parameters can be adjusted by the client (service tool ZTH-EU)

Useful additions
  • Adjustment device type ZTH (order code AT-VAV-B)
  • PC software e.g. Belimo PC-Tool or Belimo Assistant App (requires interface converter)

Technical information

  • Function
  • SPECIFICATION TEXT
  • ORDER CODE
  • TECHNICAL DATA
BM0-D8-Function

1 Differential pressure transducer
2 Actuator
3 Volume flow controller
4 Setpoint signal

Air volume flow controllers are characterised by a closed-loop control system for the regulation of air volume flow, comprising measurement, comparison and actuation.
The volume flow is obtained by measuring a differential pressure.
This is done via a differential pressure sensor. The integrated differential pressure transducer converts the differential pressure into a voltage signal. The actual volume flow rate is available as a voltage signal. Due to factory settings, 10 V DC always corresponds to the nominal volume flow (qvnom).
The volume flow setpoint is specified by a higher-level controller (e.g. room temperature controller, air quality controller, building management system). Variable volume flow control can be set between qvmin and qvmax. It is possible to override the room temperature control by override control, e.g. via a shut-off.
The controller compares the volume flow setpoint to the current actual value and controls the actuator according to the system deviation.
This specification text describes the general properties of the product. Texts for variants can be generated with our Easy Product Finder design programme.


Category
  • Compact controller for volume flow rate

Application
  • Control of a constant or variable volume flow setpoint
  • Electronic controller for applying a setpoint and acquiring an actual value for integration into a Modbus RTU or BACnet MS/TP-based management and control equipment (MCE)
  • The actual value is referenced to the nominal volume flow, simplifying commissioning and subsequent adjustment

Area of application
  • Dynamic transducer for clean air in ventilation and air conditioning systems

Actuator
  • Integrated; slow-running (travel time approx. 120 – 150 s for 90°)

Installation orientation
  • Either direction

Connection
  • 2x connector socket RJ45, for daisy-chain wiring for up to 4 control components; particularly suitable for TROX Oₓ field modules

Supply voltage
  • 24 V AC/DC

Interface/signalling
  • Modbus RTU (RS-485)
  • BACnet MS/TP
  • Power supply and communication not galvanically isolated
  • Switchable termination

Interface information
  • Modbus Register
  • BACnet objects
  • Volume flow setpoint and actual value, damper blade position, error status, etc.

System connections
  • Modbus-RTU / BACnet-MS/TP connection for optional expansions, e.g. TROX Oₓ

Special functions
  • Activation of Vmin, Vmax, Closed, Open via Modbus register or BACnet object
Operating modes that can be activated as an option
  • Open loop: actuators with airflow rate measurement

Parameter setting
  • Für VVS-Regelgerät spezifische Parameter werkseitig parametriert
  • Betriebswerte Vmin, Vmax und Schnittstellentyp werkseitig parametriert
  • Nachträgliche Anpassung mittels Modbus- / BACnet Buszugriff oder TROX Ox System Controller oder optionalen Tools (Einstellgerät, PC-Software jeweils kabelgebunden)

Factory condition
  • Functional test under air using reference measurement on a regularly validated test rig in accordance with DIN EN ISO 9001 to check the function and control accuracy of the complete volume flow controller
  • Adjustment of the device-specific parameters under air by reference measurement on a regularly validated test rig if in accordance with DIN EN ISO 9001
  • The test report of the factory parameterisation, functional test and adjustment must be made available after delivery of the volume flow controller

Equivalence criteria
  • The test report of the factory parameterisation, functional test and adjustment under air by reference measurement on a regularly validated test rig in accordance with DIN EN ISO 9001 is provided
TVRDP1/250/D2/BM0-D8/V/500 – 1200 [m³/h]
|||||||||
123456789

1 Type
TVR VAV terminal unit


2 Acoustic cladding
No entry: without acoustic cladding
D with acoustic cladding


3 Material
No entry: galvanised sheet steel
P1 Surface powder-coated, RAL 7001 (silver grey)
A2 Stainless steel variant


4 Air duct connection
No entry: push-fit end for air ducts according to DIN EN 1506; with groove for optional seal
FL Flange on both sides (not for TVR-D-P1 or TVR-D-A2)


5 Nominal size [mm]
100, 125, 160, 200, 250, 315, 400


6 Accessories
No entry: without accessories
D2 Double lip seal on both ends
G2 Matching flanges on both ends


7 Attachment (control component)
BM0-D8 Compact controller with dynamic transducer and Modbus RTU bus interface as well as 2 RJ45 connection sockets for TROX Oₓ


8 Operating mode
V variable operation (adjustable setpoint range)


9 Operating values for factory setting
Volume flow rate [m3/h or l/s]
qᵥmin – qᵥmax

Order example: TVR-D-P1/250/D2/BM0-D8/V/500-1200[m³/h]
TypeTVR – VAV terminal unit
Acoustic claddingwith acoustic cladding
MaterialSurface powder-coated, RAL 7001 (silver grey)
Air duct connectionPush-fit end, suitable for air ducts according to EN 1506; with groove for optional lip seal
Nominal size [mm]250
AccessoriesDouble lip seal on both ends
Attachments (control component)BM0-D8 - Compact controller with dynamic transducer and Modbus RTU bus interface as well as 2 RJ45 connection sockets for TROX Oₓ
Operating statevariable operation (adjustable setpoint range)
Operating values for factory setting500 – 1200 [m3/h]

Compact controller for VAV terminal units

VAV terminal units

Type of attachment

Part number

TVR1

LMV-D3-M/B-FX TR

P0012126

TVR2, TZ-Silenzio, TA-Silenzio, TVZ, TVA

LMV-D3-M/B-X TR

P0012124

TVM

2x LMV-D3-M/B-X TR

P0012124

TVJ, TVT

NMV-D3-M/B-X TR

P0012125

  1. TVR Initial equipment
  2. TVR Spare part


Compact controller BM0-D8, type LMV-D3-M/B-X TR (clamping bracket)

Compact controller BM0-D8, Typ LMV-D3-M/B-FX TR (positive locking)


Compact controller BM0-D8, LMV-D3-M/B-X TR (clamping bracket) and LMV-D3-M/B-FX TR (positive locking)

Measuring principle / installation orientation

dynamic measuring principle, independent of position

Rated voltage

24 V AC/DC

Rated voltage (frequency)

50/60 Hz

Functional range

AC 19.2 – 28.8 V/DC 21.6 – 28.8 V

Power consumption – operating/standby

2 W/1 W

Power consumption – sizing/inrush current

4 VA 8.0 A @ 5 ms

Bus connection

Interface RS485 – protocol Modbus** RTU, BACnet MS/TP


Modbus RTU communication parameters to be set

Baud rate: 9600, 19200, 38400**, 76800, 115200;

Address: 1**, 2, 3 – 247;

Parity: 1-8-N-2**, 1-8-N-1, 1-8-E-1, 1-8-O-1;

Number of nodes: max. 32 (without repeater)

Termination resistor: 120 Ω;


BACnet MS/TP communication parameters to be set

Baud rate: 9600, 19200, 38400, 76800, 115200;

Address: 0,1, 2, 3 – 127;

Number of nodes: max. 32 (without repeater)

Termination resistor: 120 Ω;

Addressing

required on site: e.g. adjustment device ZTH-EU or external

software

Bus termination

internal connection resistor 120 Ω can be activated


Maximum bus structure daisy-chain wiring

Loop-through: maximum 4 control components type BM0-D8, Distance between two control components: maximum 3 m

Total cable length: maximum 40 m

Torque

5 Nm

Setpoint/actual value interface

via Modbus register access, e.g. via TROX Ofield module

alternatively via BACnet objects


Connections

RJ45-Doppelanschlussbuchse ungeschirmt, maximal 1 A / 20 W pro Strang

Verkabelung: ungekreuztes Patchkabel AWG24 nach TIA T586A

IEC protection class

III (protective extra-low voltage)

Protection degree (IP code)

IP 20

Weight

0.55 kg

EC conformity

EMC according to 2014/30/EU

**Factory setting

Compact controller BM0-D8, NMV-D3-M/B-X TR (clamping bracket)


Compact controller BM0-D8, type NMV-D3-M/B-X TR (clamping bracket)

Measuring principle / installation orientation

dynamic measuring principle, independent of position

Rated voltage

24 V AC/DC

Rated voltage (frequency)

50/60 Hz

Functional range

AC 19.2 – 28.8 V/DC 21.6 – 28.8 V

Power consumption – operating/standby

3 W/1.5 W

Power consumption – sizing/inrush current

4 VA 8.0 A @ 5 ms

Bus connection

Interface RS485 – protocol Modbus** RTU, BACnet MS/TP


Modbus RTU communication parameters to be set

Baud rate: 9600, 19200, 38400**, 76800, 115200;

Address: 1**, 2, 3 – 247;

Parity: 1-8-N-2**, 1-8-N-1, 1-8-E-1, 1-8-O-1;

Number of nodes: max. 32 (without repeater)

Termination resistor: 120 Ω;


BACnet MS/TP communication parameters to be set

Baud rate: 9600, 19200, 38400, 76800, 115200;

Address: 0,1, 2, 3 – 127;

Number of nodes: max. 32 (without repeater)

Termination resistor: 120 Ω;

Addressing

required on site: e.g. adjustment device ZTH-EU or external

software

Bus termination

internal connection resistor 120 Ω can be activated


Maximum bus structure daisy-chain wiring

Loop-through: maximum 4 control components type BM0-D8 Distance between two control components: maximum 3 m

Total cable length: maximum 40 m

Torque

10 Nm

Setpoint/actual value interface

via Modbus register access, e.g. via TROX Ofield module

alternatively via BACnet objects


Connections

RJ45-Doppelanschlussbuchse ungeschirmt,

maximal 1 A / 20 W pro Strang

Verkabelung: ungekreuztes Patchkabel AWG24 nach TIA T586A

IEC protection class

III (protective extra-low voltage)

Protection degree (IP code)

IP 20

Weight

0.83 kg

EC conformity

EMC according to 2014/30/EU

**Factory setting

Downloads

product information

production {"x-frame-options"=>"SAMEORIGIN", "x-xss-protection"=>"1; mode=block", "x-content-type-options"=>"nosniff", "x-download-options"=>"noopen", "x-permitted-cross-domain-policies"=>"none", "referrer-policy"=>"strict-origin-when-cross-origin", "strict-transport-security"=>"max-age=31536000; includeSubDomains", "content-type"=>"text/html; charset=utf-8"}

Share page

Recommend this page

Recommend this page by sending a link by mail.

Fields marked with an (*) are required fields.

Share page

Thank you for your recommendation!

Your recommendation has been sent and should arrive shortly.

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Contact

We are here for you

Please specify your message and type of request
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265

Attachment (max. 10MB)

Fields marked with an (*) are required fields.

Contact

Thank you for your message!

Your message is send and will be processed shortly.
Our department for Service-Requests will contact you asap.
For general question regarding products or services you can also call:
Tel.: +49 (0)2845 / 202-0 | Fax: +49 (0)2845/202-265